STPS-KN Quick-switching emergency power supply

Product Description

EPS power supply, also known as fire emergency power supply, with the full name of Emergency Power Supply (emergency power supply), is an emergency power supply adopted in important buildings nowadays for power guarantee and fire safety. It mainly consists of input and output units, charging modules, battery packs, inverters, monitors, output switching devices, etc. It is widely used in chemical plants, oil fields, hospitals, schools, shopping malls, sports venues, exhibition centers, financial systems, subways, high-speed railway stations, tunnels, expressways and other places.

Product Application

The fast-switching EPS power supply is specifically designed for primary loads, fire protection facilities, fire emergency lighting, or other equipment that requires uninterrupted emergency power supply. In the event of abnormal mains power, it provides centralized and uninterrupted emergency power supply for the electrical load.


Product Features

The switching device uses static thyristor switching, which has a fast switching speed.
2. Utilizing imported IGBT/IPM intelligent power modules, ensuring high reliability
3. Utilizing advanced DSP digital control technology, providing pure sine wave output
4. Equipped with a mandatory emergency start switch and an automatic/manual switching switch
5. The monitoring system uses fully localized LCD liquid crystal display, making the system operation data clearly visible at a glance.
6. Equipped with fire linkage control and fire center control functions
7. Fully automatic and intelligent battery management function

Product advantages

1.The switching time is short, enabling uninterrupted switching.
2. Fully digital control, automatic switching, achieving unmanned operation
3. Simple design, easy construction
4. Stable performance, safe and reliable, long service life
5. Energy-saving. When not in emergency power mode, it consumes almost no electricity.
6. Maintenance-free battery, capable of being recharged up to 300-500 times.

Specifications
STPS-KN-2.2~400kVA
capacity
2.2~400kW
Input characteristics
 
Voltage
AC380V(-15~+20%)
Frequency
50Hz±5%
Wiring method
Three-phase four-wire system
Battery Characteristics
 
Battery Type
Sealed maintenance-free lead-acid battery
Rated voltage
DC96V/DC192V/DC324V/DC480V
Charging Current
3~20A
Charging time
<24h
Charging method
Automatic conversion between average charge and floating charge
Backup time
90/180min(Or you can choose according to your needs)
Output Characteristics
When the mains power is normal, it is consistent with the mains power; it should be timely, AC380±3%
Voltage
When the mains power is normal, it is consistent with the mains power; it should be timely, 50Hz±0.1%
Frequency
At 105%–120% load, the system operates normally while emitting a warning sound; at 120%–150% load, in emergency mode, it will
automatically switch on and off after one minute or switch to mains mode when input power is restored; above 150% load, in
emergency mode, it will automatically switch on and off within 10 milliseconds or switch to mains mode when input power is
available.
Overload capability
3:1
Peak ratio
In emergency, pure sine wave
Output waveform
 
Environmental characteristics
In emergency, pure sine wave
Relative humidity
10%~90%no fog
Ambient temperature
-10°C~45°C
Altitude
≤3000m
Other features
 
Switching time
<3ms
Protection function
Input undervoltage protection (can be forcibly overridden); output overload, short-circuit protection, overheat protection, etc
Cooling method
Forced air cooling
Noise
in emergency mode, the noise level is less than 55 dB at a distance of 1meter
Load type
Suitable for various loads
5/5
Would you like me to tailor this to a specific industry or service?
WE TAILOR OUR SOLUTIONS TO FIT YOUR UNIQUE NEEDS. LET US KNOW YOUR REQUIREMENTS, AND WE’LL CREATE A PERSONALIZED PLAN.