KN-H33 three-in and three-out high-frequency online type

Features

  1. Digital control technology, ensuring a more stable and reliable control system.

  2. Double-conversion online design, with input power factor up to 0.99.

  3. Output power factor up to 0.9 (0.8 optional), providing higher actual load capacity.

  4. Intelligent charging management, with selectable battery quantity (32–40 batteries configurable).

  5. Rich optional accessories, including USB or RS232, SNMP card, parallel card, and relay card.

  6. ECO operating mode, offering high efficiency and energy savings to reduce user costs.

  7. Parallel redundancy function, supporting up to 4 units in parallel, sharing a common battery bank.

  8. Four convertible modes, including three-phase input & three-phase output, three-phase input & single-phase output, single-phase input & three-phase output, and single-phase input & single-phase output.

Product Name:
KN-H33 three-in and three-out high-frequency on-line type
Technical parameters
Model
KN-H33/10KVA
KN-H33/20KVA
KN-H33/30KVA
KN-H33/40KVA
Capacity
10KVA/9KW
20KVA/18KW
30KVA/27KW
40KVA/36KW
Input characteristics
Input method
Three-phase four-wire + grounding
 
Rated voltage
380/400/415VAC
 
Voltage range
208~478VAC
 
Frequency range
45~55Hz/54~66Hz(Adaptive)
 
Power factor
≥0.99
 
Input current harmonic
≤3% (100% nonlinear load)
 
Bypass range
Upper limit of bypass protection voltage: 220V:+25%(optional +10%, +15%, +20%
 
 
230V:+20%(Optional +10%, +15%)
 
 
240V:+15%(optional +10%)
 
 
Lower limit of bypass protection voltage: -45% (optional -20%, 30%)
 
 
Bypass frequency protection range: ±10%
Output characteristics
Output mode
Three-phase four-wire + grounding
 
Rated voltage
380/400/415VAC
 
Power factor
0.9
 
Voltage accuracy
±1%
 
Output frequency
Mains power mode
Synchronize with the input; When the mains power frequency exceeds the maximum ±10% (which can be set as ±1%, ±2%, ±4%, or ±5%),
the output frequency is 50× (±0.2) Hz
 
 
Battery mode
50/60Hz±0.2%
 
Load peak ratio
3:1
 
Output voltage distortion
≤2% (linear load)
 
 
≤5% (nonlinear load)
Efficiency
 
Normal mode ≥94.5%
Battery characteristics
Battery voltage
±192VDC(32 sections)
 
Charging current
10Amax
Switching time
 
Mains power mode to bypass mode: 0ms (tracking) Mains power mode to battery mode: 0ms
Protection function
Overload capacity
Load ≤110% for 60 minutes; ≤125% 10 minutes; ≤150% 1 minute; Shut down immediately when it exceeds 150%
 
Over-temperature ability
Normal mode: Switch to bypass mode; Battery mode: Immediately turn off the output
 
Emergency Shutdown (EP0)
Turn off the output immediately
Communication interface
 
USB,RS485, dry contact, parallel operation (optional), SNMP card (optional), relay card (optional)
Working environment
Working temperature
0~40℃
 
Relative humidity
0-95% (no condensation)
 
Storage temperature
-25~+55℃
 
Altitude
< 1500m, (above 1500m, use a reduced limit)
Physical properties
Dimensions (depth, width, height) in millimeters
828×250×800 (standard model), 680×250×540 (long model)
 
Weight (net weight) Kg
123/45
123/45
126/46
128/48
enforce standards
 
YD/T1095-2008
5/5